5500 Fire-Tite UL Fire Dampers Thin 2 Frame

CLICK HERE FOR PRINTABLE/ELECTRONIC SUBMISSION PDF

Vent_5512 Vent_5512 Vent_5512dim1 Vent_5512dim2 Vent_5500aul

STANDARD SPECIFICATIONS

  • MATERIALS: Standard construction-galvanized steel.
    Specifications for all material per Underwriters Laboratories Standard for Safety UL555.
  • MINIMUM SIZE: 4"x4"
  • MAXIMUM DUCT OPENING SINGLE SECTION: VERTICAL: 41" x 36" or 36" x 60"
    HORIZONTAL: 41" x 36"
  • SPECIAL TYPES: Variations of 2" deep channel frame are available incorporating the Type B, Type C or Type CR construction. Models 5522, 5523, 5532, 5533, 5542, 5543, 5552 and 5553.
  • UNDERWRITERS LABORATORIES: Labelled for use in sizes no larger than shown in U.L. Building Materials List in a 2 hour fire partition

OPTIONS

  • - Optional 304 Stainless Steel Construction Available
  • - Optional 212°F Fusible Link Available.

NOTES

  1. ALL DAMPERS 1/4" UNDER LISTED DIMENSIONS
  2. Meets N.F.P.A. 90A Requirements.
  3. Sizes shown are for Type A construction. Consult Factory for Type B, Type C and Type CR.